Page 1 - Generator Systems

Questions? Help is just a moment away!Call: Generator Helpline877-369-9400 Monday-Friday 8:00 AM to 5:00 PM Central TimeGenerator SystemsInstallati

Page 2 - Generator

10 Intentionally Left Blank

Page 3 - Table of Contents

11Generator PlacementBefore installing generator, consult with home owner and convey the following requirements, which must be satisfied before the

Page 4 - Save These Instructions

12 All fossil fuel burning equipment, such as standby generators, contains carbon monoxide (CO) gas in the engine exhaust. CO gas is odorless, colorle

Page 5

13 t %JSFDUUIFTUBOECZHFOFSBUPSFYIBVTUBXBZGSPNPSparallel to the building or structure. DO NOT direct the generator exhaust towards a potent

Page 6

14 Placement of Standby Generator to REDUCE THE RISK OF FIRERequirements:NFPA 37 2010, section 4. 1. 4, Engines Located Outdoors. Engines, and their

Page 7 - Installation

15 A Standby weatherproof enclosure must be at least 5 ft (1.5 m) from windows, doors, any wall opening, shrubs or vegetation over 12 inches (30.5

Page 8 - Shipment Contents

16 Electrical and Fuel Inlet LocationsThe 3/4 inch N.P.T. fuel inlet connector (A) and electrical inlet location (B) is shown below.A ½ inch knock-out

Page 9 - Installation Checklist

17Lifting the GeneratorThe generator weighs more than 500 pounds (227 kg). Proper tools, equipment and qualified personnel should be used in all pha

Page 10 - Intentionally Left Blank

18 Access PortsThe generator is equipped with an enclosure that has several access panels, as shown. The access panels and the components located behi

Page 11 - Exhaust Side of the Generator

19To open roof: 1. Insert key into lock (A) of front panel. Gently push down on roof above the lock to aid in turning the key. Turn key one quarte

Page 12

Thank you for purchasing this quality-built Rheem / Ruud standby generator. We are pleased that you’ve placed your confidence in the Rheem or Ruud bra

Page 13 - GENERATOR

20 The Gaseous Fuel SystemThe information below is provided to assist gaseous fuel system technicians in planning installations. In no way should this

Page 14 - RISK OF FIRE

21Fuel ConsumptionEstimated fuel supply requirements at half and full load for natural gas and LP vapor fuels are shown below.LP Vapor (Propane)20kW

Page 15

22 Fuel ConversionThe engine of your generator system is factory calibrated to run on natural gas (NG) or on liquefied petroleum (LP) vapor. To conver

Page 16

23System ConnectorsLow Voltage connections to signal fault contacts, transfer switch communication and auxiliary 12VDC power are made via a field co

Page 17 - Concrete Anchoring of Unit

24 Generator AC Connection SystemA single-phase, three-wire AC connection system is used in the home generator. The stator assembly consists of a pair

Page 18 - Access Ports

25Grounding the GeneratorThe home generator must be installed as part of a system that includes a listed transfer switch, with neutral to ground bon

Page 19

26 System Control PanelThe generator control panel, located inside the generator housing, is shown below.Brief descriptions of the controls used durin

Page 20 - The Gaseous Fuel System

27Menu MENUENTER THE MENU (VIEW SETTINGS) PRESS TO CONFIRM SELECTION WHEN PROGRAMMING.ESCAPE (EXIT) RETURN TO LAST MENU ITEMRIGHT ARROWTOGGLE THROU

Page 21

28 NOTE: Date and Time were set at the factory and stored in the control panel memory. The Exercise Cycle wasalso set at the factory. The default exer

Page 22 - Fuel Conversion

29AUTOMATIC MODEGENERATOR ON(When Generator Running - Auto Mode)GENERATOR READY or SERVICE CODE DESCRIPTION(When Generator NOT Running - Auto Mode)C

Page 23 - System Connectors

3Table of ContentsImportant Safety Instructions...4Installation ...7Owner Responsibilities...

Page 24

30 Advanced Settings Screen kWkWFLASHING50/60 HzFLASHING Hz PHASE VOLTSSOFTWAREVersion DisplayedVOLTSFLASHINGSINGLEorTHREEFLASHING E-GovernorCheckStep

Page 25 - Transfer Switch Communication

31Final Installation ConsiderationsEngine OilNOTICE Any attempt to crank or start the engine before it has been properly serviced with the recommend

Page 26 - System Control Panel

32 Initial Start-up (No Load)The unit has been set-up for NG operation at the factory. Fuel conversion, if needed, must be completed prior to performi

Page 27

33Electronic Governor System The engine electronic governor system allows for improved control and increased generator performance compared to mecha

Page 28 - General Set Up Screen

34 OperationAutomatic Operation SequenceThe generator’s control board constantly monitors utility voltage. Should utility voltage drop below a preset

Page 29 - EXERCISE CYCLE

35Antenna InstallationThe supplied antenna must be installed before the wireless monitor will operate. 1. Insert key into lock of front panel. Ge

Page 30 - Stepper Motor

36 Wireless MonitorThe generator is supplied with a battery-powered, wireless monitor.The monitor communicates wirelessly with the generator control p

Page 31 - Service Code Detection System

37Wireless Monitor Operation 1. Remove battery access cover (A) on back of monitor and install 2 AA batteries. (Observe correct battery polarity w

Page 32 - Initial Start-up (No Load)

38 Standard Operation:Wireless Monitor Status LED’s t 5IFXJSFMFTTNPOJUPSSFDFJWFTEBUBGSPNUIFHFOFSBUPSevery 10 minutes and displays the genera

Page 33 - Electronic Governing Check:

39Schematic DiagramSchematic / Wiring DiagramsLEGENDBW - Plug for Optional Battery WarmerCB - Circuit BreakerCMA - Control Module AssemblyCOM - Comm

Page 34 - Operation

4 Save These Instructions WARNING Running engine gives off carbon monoxide, an odorless, colorless, poison gas. Breathing carbon monoxide could result

Page 35 - Antenna Installation

40 LEGENDBW - Plug for Optional Battery WarmerCB - Circuit BreakerCMA - Control Module AssemblyCOM - CommonEW - Plug for Optional Engine Oil WarmerFS

Page 36 - Wireless Monitor

5 WARNING Generator produces hazardous voltage. Failure to properly ground generator could result inelectrocution. Failure to isolate generator fr

Page 37 - Wireless Monitor Operation

6 WARNING Starter and other rotating parts could entangle hands, hair, clothing, or accessories resulting in serious injury.t NEVER operate generato

Page 38 - Installation Inspection

7InstallationEquipment DescriptionThis product is only for use as an optional generator system which provides an alternate source of electric power

Page 39 - Schematic / Wiring Diagrams

8 Unpacking PrecautionsThe unit is shipped ready for installation. Avoid damage from dropping, bumping, collision, etc. Store and unpack carton with t

Page 40 - Wiring Diagram

9Installation ChecklistCarbon Monoxide (CO) Detector Carbon Monoxide (CO) detector installed and in working order. Smoke detector(s) install