Air
Gross Systems Performance Data
RRNL Series
32
GROSS SYSTEMS PERFORMANCE DATA—B048
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1760 [831] 1600 [755] 1440 [680] 1760 [831] 1600 [755] 1440 [680] 1760 [831] 1600 [755] 1440 [680]
DR
.22 .20 .19 .22 .20 .19 .22 .20 .19
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
61.6 [18.05]
34.8 [10.20]
3.0
60.5 [17.73]
33.2 [9.73]
2.9
59.4 [17.41]
31.7 [9.29]
2.9
58.0 [17.00]
41.6 [12.19]
2.9
57.0 [16.71]
39.7 [11.63]
2.9
55.9 [16.38]
37.9 [11.11]
2.9
55.3 [16.21]
44.4 [13.01]
2.9
54.3 [15.91]
42.4 [12.43]
2.9
53.3 [15.62]
40.4 [11.84]
2.9
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
59.9 [17.55]
33.7 [9.88]
3.1
58.8 [17.23]
32.2 [9.44]
3.1
57.7 [16.91]
30.7 [9.00]
3.1
56.2 [16.47]
40.5 [11.87]
3.1
55.2 [16.18]
38.7 [11.34]
3.1
54.2 [15.88]
36.9 [10.81]
3.1
53.5 [15.68]
43.3 [12.69]
3.1
52.6 [15.42]
41.4 [12.13]
3.1
51.6 [15.12]
39.4 [11.55]
3.1
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
58.2 [17.06]
32.8 [9.61]
3.3
57.1 [16.73]
31.3 [9.17]
3.3
56.1 [16.44]
29.8 [8.73]
3.3
54.5 [15.97]
39.6 [11.61]
3.3
53.5 [15.68]
37.8 [11.08]
3.3
52.6 [15.42]
36.0 [10.55]
3.2
51.8 [15.18]
42.3 [12.40]
3.3
50.9 [14.92]
40.4 [11.84]
3.3
49.9 [14.62]
38.6 [11.31]
3.2
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
56.4 [16.53]
31.9 [9.35]
3.5
55.4 [16.24]
30.4 [8.91]
3.5
54.4 [15.94]
29.0 [8.50]
3.4
52.8 [15.47]
38.7 [11.34]
3.5
51.8 [15.18]
36.9 [10.81]
3.4
50.9 [14.92]
35.2 [10.32]
3.4
50.1 [14.68]
41.4 [12.13]
3.5
49.2 [14.42]
39.6 [11.61]
3.4
48.3 [14.16]
37.7 [11.05]
3.4
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
54.7 [16.03]
31.0 [9.09]
3.7
53.7 [15.74]
29.6 [8.67]
3.6
52.7 [15.44]
28.2 [8.26]
3.6
51.0 [14.95]
37.8 [11.08]
3.7
50.1 [14.68]
36.1 [10.58]
3.6
49.2 [14.42]
34.4 [10.08]
3.6
48.3 [14.16]
40.6 [11.90]
3.6
47.4 [13.89]
38.7 [11.34]
3.6
46.6 [13.66]
36.9 [10.81]
3.6
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
52.9 [15.50]
30.1 [8.82]
3.9
51.9 [15.21]
28.8 [8.44]
3.8
51.0 [14.95]
27.4 [8.03]
3.8
49.2 [14.42]
36.9 [10.81]
3.8
48.3 [14.16]
35.3 [10.35]
3.8
47.5 [13.92]
33.6 [9.85]
3.8
46.5 [13.63]
39.7 [11.63]
3.8
45.7 [13.39]
37.9 [11.11]
3.8
44.8 [13.13]
36.1 [10.58]
3.8
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
51.0 [14.95]
29.2 [8.56]
4.0
50.1 [14.68]
27.9 [8.18]
4.0
49.2 [14.42]
26.6 [7.80]
4.0
47.3 [13.86]
36.0 [10.55]
4.0
46.5 [13.63]
34.4 [10.08]
4.0
45.6 [13.36]
32.8 [9.61]
3.9
44.6 [13.07]
38.8 [11.37]
4.0
43.8 [12.84]
37.0 [10.84]
4.0
43.0 [12.60]
35.3 [10.35]
3.9
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
49.0 [14.36]
28.2 [8.26]
4.2
48.1 [14.10]
27.0 [7.91]
4.2
47.2 [13.83]
25.7 [7.53]
4.1
45.3 [13.28]
35.0 [10.26]
4.2
44.5 [13.04]
33.5 [9.82]
4.2
43.7 [12.81]
31.9 [9.35]
4.1
42.6 [12.48]
37.8 [11.08]
4.2
41.9 [12.28]
36.1 [10.58]
4.1
41.1 [12.05]
34.4 [10.08]
4.1
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
46.9 [13.75]
27.1 [7.94]
4.4
46.1 [13.51]
25.9 [7.59]
4.4
45.2 [13.25]
24.7 [7.24]
4.3
43.2 [12.66]
33.9 [9.94]
4.4
42.5 [12.46]
32.4 [9.50]
4.3
41.7 [12.22]
30.9 [9.06]
4.3
40.5 [11.87]
36.7 [10.76]
4.4
39.8 [11.66]
35.1 [10.29]
4.3
39.1 [11.46]
33.4 [9.79]
4.3
GROSS SYSTEMS PERFORMANCE DATA—C060
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 2040 [963] 1850 [873] 1660 [783] 2040 [963] 1850 [873] 1660 [783] 2040 [963] 1850 [873] 1660 [783]
DR
.21 .20 .18 .21 .20 .18 .21 .20 .18
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
73.6 [21.57]
42.2 [12.37]
4.0
72.3 [21.19]
40.3 [11.81]
3.9
71.0 [20.81]
38.4 [11.25]
3.9
68.5 [20.08]
49.1 [14.39]
3.9
67.3 [19.72]
46.9 [13.75]
3.8
66.1 [19.37]
44.7 [13.10]
3.8
65.9 [19.31]
53.3 [15.62]
3.8
64.7 [18.96]
50.9 [14.92]
3.8
63.5 [18.61]
48.5 [14.21]
3.7
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
71.3 [20.90]
40.7 [11.93]
4.2
70.0 [20.51]
38.9 [11.40]
4.1
68.7 [20.13]
37.1 [10.87]
4.1
66.2 [19.40]
47.7 [13.98]
4.1
65.0 [19.05]
45.5 [13.33]
4.0
63.9 [18.73]
43.4 [12.72]
4.0
63.6 [18.64]
51.8 [15.18]
4.0
62.4 [18.29]
49.5 [14.51]
4.0
61.3 [17.97]
47.2 [13.83]
3.9
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
69.3 [20.31]
39.5 [11.58]
4.4
68.1 [19.96]
37.8 [11.08]
4.4
66.8 [19.58]
36.0 [10.55]
4.3
64.2 [18.82]
46.5 [13.63]
4.3
63.1 [18.49]
44.4 [13.01]
4.3
61.9 [18.14]
42.3 [12.40]
4.2
61.6 [18.05]
50.6 [14.83]
4.2
60.5 [17.73]
48.3 [14.16]
4.2
59.4 [17.41]
46.1 [13.51]
4.1
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
67.5 [19.78]
38.5 [11.28]
4.6
66.3 [19.43]
36.8 [10.79]
4.6
65.1 [19.08]
35.1 [10.29]
4.5
62.5 [18.32]
45.5 [13.33]
4.5
61.3 [17.97]
43.5 [12.75]
4.5
60.2 [17.64]
41.4 [12.13]
4.4
59.8 [17.53]
49.6 [14.54]
4.4
58.7 [17.20]
47.4 [13.89]
4.4
57.6 [16.88]
45.2 [13.25]
4.4
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
65.8 [19.28]
37.7 [11.05]
4.8
64.7 [18.96]
36.0 [10.55]
4.8
63.5 [18.61]
34.3 [10.05]
4.7
60.8 [17.82]
44.6 [13.07]
4.7
59.7 [17.50]
42.6 [12.48]
4.7
58.6 [17.17]
40.7 [11.93]
4.6
58.1 [17.03]
48.8 [14.30]
4.6
57.1 [16.73]
46.6 [13.66]
4.6
56.0 [16.41]
44.4 [13.01]
4.6
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
64.2 [18.82]
36.9 [10.81]
5.0
63.0 [18.46]
35.3 [10.35]
5.0
61.9 [18.14]
33.6 [9.85]
4.9
59.1 [17.32]
43.9 [12.87]
4.9
58.0 [17.00]
41.9 [12.28]
4.9
57.0 [16.71]
39.9 [11.69]
4.8
56.4 [16.53]
48.0 [14.07]
4.9
55.4 [16.24]
45.8 [13.42]
4.8
54.4 [15.94]
43.7 [12.81]
4.8
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
62.4 [18.29]
36.1 [10.58]
5.2
61.3 [17.97]
34.5 [10.11]
5.2
60.1 [17.61]
32.9 [9.64]
5.2
57.3 [16.79]
43.1 [12.63]
5.1
56.3 [16.50]
41.2 [12.07]
5.1
55.3 [16.21]
39.2 [11.49]
5.1
54.6 [16.00]
47.2 [13.83]
5.1
53.7 [15.74]
45.1 [13.22]
5.0
52.7 [15.44]
43.0 [12.60]
5.0
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
60.4 [17.70]
35.3 [10.35]
5.5
59.3 [17.38]
33.7 [9.88]
5.4
58.2 [17.06]
32.2 [9.44]
5.4
55.3 [16.21]
42.3 [12.40]
5.4
54.3 [15.91]
40.4 [11.84]
5.3
53.4 [15.65]
38.5 [11.28]
5.3
52.7 [15.44]
46.4 [13.60]
5.3
51.7 [15.15]
44.3 [12.98]
5.2
50.8 [14.89]
42.2 [12.37]
5.2
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
58.1 [17.03]
34.4 [10.08]
5.7
57.1 [16.73]
32.8 [9.61]
5.6
56.0 [16.41]
31.3 [9.17]
5.6
53.0 [15.53]
41.3 [12.10]
5.6
52.1 [15.27]
39.5 [11.58]
5.5
51.1 [14.98]
37.6 [11.02]
5.5
50.4 [14.77]
45.4 [13.31]
5.5
49.5 [14.51]
43.4 [12.72]
5.4
48.6 [14.24]
41.4 [12.13]
5.4
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible