PACKAGE HEAT PUMP UNITS
RJNA- HIGH EFFICIENCY SERIES
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
*Unit shown with
optional louver
panels installed.
“CERTIFIED UNDER THE
A.R.I. CERTIFICATION
PROGRAM—A.R.I.
STANDARD 240”
ISO 9001:2000
Page view 0
1 2 3 4 5 6 ... 49 50

Summary of Contents

Page 1 - PACKAGE HEAT PUMP UNITS

FORM NO. P11-763 REV. 1Supersedes Form No. P11-763PACKAGE HEAT PUMP UNITS RJNA- HIGH EFFICIENCY SERIESNOMINAL SIZES 3-5 TONS [10.6-17.6 kW]*Unit shown

Page 2 - TABLE OF CONTENTS

10GENERAL DATA—RJNA- SERIESModel RJNA- Series A042DM A042JK A048CK A048CLCooling Performance1Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12

Page 3 - Outdoor Package Heat Pumps

11GENERAL DATA—RJNA- SERIESModel RJNA- Series A048CM A048DK A048DL A048DMCooling Performance1Gross Cooling Capacity Btu [kW] 49,500 [14.5] 49,500 [14

Page 4 - INTRODUCTIONINTRODUCTION

12GENERAL DATA—RJNA- SERIESModel RJNA- Series A048JK A060CK A060CL A060CMCooling Performance1Gross Cooling Capacity Btu [kW] 49,500 [14.5] 63,500 [18

Page 5 - RJNA—A036JK000

13GENERAL DATA—RJNA- SERIESModel RJNA- Series A060DL A060DM A060JKCooling Performance1Gross Cooling Capacity Btu [kW] 64,000 [18.8] 64,000 [18.8] 63,

Page 6 - OPTIONS—RJNA- SERIES

14GENERAL DATA—RJNA- SERIESNOTES:1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity do

Page 7

COOLING PERFORMANCE DATA—RJNA-A036HEATING PERFORMANCE DATA—RJNA-A036DR —Depression ratiodbE —Entering air dry bulbwbE—Entering air wet bulbTotal —Tota

Page 8

COOLING PERFORMANCE DATA—RJNA-A042HEATING PERFORMANCE DATA—RJNA-A042DR —Depression ratiodbE —Entering air dry bulbwbE—Entering air wet bulbTotal —Tota

Page 9

COOLING PERFORMANCE DATA—RJNA-A048DR —Depression ratiodbE —Entering air dry bulbwbE—Entering air wet bulbTotal —Total capacity x 1000 BTUHSens —Sensib

Page 10 - GENERAL DATA—RJNA- SERIES

COOLING PERFORMANCE DATA—RJNA-A060HEATING PERFORMANCE DATA—RJNA-A060DR —Depression ratiodbE —Entering air dry bulbwbE—Entering air wet bulbTotal —Tota

Page 11

External Static Pressure—Inches W.C. [kPa]CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—Wet Coil4.0[14.07]LowBlower Size/MotorHP [w] &

Page 12

2TABLE OF CONTENTSIntroduction ...3-4Model Identificati

Page 13

20AIRFLOW PERFORMANCE—RJNA- SERIES825Models RJNA-A036 [10.55 kW] & A042 [12.31 kW]—Heat Pump (13 SEER)External Static Pressure—Inches of Water [kP

Page 14

BELT-DRIVE AIRFLOW PERFORMANCECOMPONENT AIR RESISTANCENOTES:1. Performance shown with dry coil, standard 1" [25.4 mm] filters & side discharg

Page 15

ELECTRICAL DATA – RJNA SERIESMinimum CircuitAmpacity19/19Unit InformationUnit OperatingVoltage Range187-253Minimum OvercurrentProtection Device Size25

Page 16

ELECTRICAL DATA – RJNA SERIESMinimum CircuitAmpacityMinimum OvercurrentProtection Device Size22/2225/25Maximum OvercurrentProtection Device Size30/30C

Page 17

24UNITS WITH HEATER KITS—RJNA- SERIES*A10C+*A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80

Page 18

25UNITS WITH HEATER KITS—RJNA- SERIES*A10C+*A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 43/47 45/45 50/50*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 68/75 70/70 80

Page 19

26UNITS WITH HEATER KITS—RJNA- SERIES*A10C+*A10C+ 7.2/9.6 24.56/32.75 20.0/23.1 44/48 45/45 50/50*A20C+ 14.4/19.2 49.13/65.51 40.1/46.2 69/76 70/70 80

Page 20

27UNITS WITH HEATER KITS—RJNA- SERIES*A10D+*A10D+ 9.6 32.75 11.6 24 25 25*A20D+ 19.2 65.51 23.1 38 40 40*A12D+ 11.2 38.21 13.5 26 30 30*A15D+ 14.4 49.

Page 21 - COMPONENT AIR RESISTANCE

28UNITS WITH HEATER KITS—RJNA- SERIES*A10D+*A10D+ 9.6 32.75 11.6 24 25 25*A20D+ 19.2 65.51 23.1 38 40 40*A12D+ 11.2 38.21 13.5 26 30 30*A15D+ 14.4 49.

Page 22 - ELECTRICAL DATA—RJNA- SERIES

29UNITS WITH HEATER KITS—RJNA- SERIES*A10D+*A10D+ 9.6 32.75 11.6 24 25 25*A20D+ 19.2 65.51 23.1 38 40 40*A12D+ 11.2 38.21 13.5 26 30 30*A15D+ 14.4 49.

Page 23

3INTRODUCTIONThese quality features are included in the RheemOutdoor Package Heat PumpsEvaporator Coil/Filter AccessOptional Electric Heater KitCompre

Page 24 - + Field Installed Only

A036JKNo Heat — — — 25/25 30/35 30/35*A10J+ 7.2/9.6 24.56/32.75 34.7/40.0 69/75 70/70 80/80*A06J+ 4.2/5.6 14.33/19.10 20.2/23.3 51/55 60/60 60/60*A11J

Page 25

UNIT DIMENSIONSPACKAGEHEAT PUMPS[ ] Designates Metric Conversions31UNIT DIMENSIONS—RJNA- SERIES

Page 26

UNIT DIMENSIONSPACKAGEHEAT PUMPS[ ] Designates Metric ConversionsBOTTOM VIEW32UNIT DIMENSIONS—RJNA- SERIES

Page 27

SELECTION PROCEDURE1. Determine cooling and heating requirements at design conditions.Example:Total cooling capacity ...43,600 BTUH [12.78 kW

Page 28

AccessoryDescriptionModel Application3 to 5 Ton[10.6 to 17.6 kW]AccessoryModel No.3 to 5 Ton[10.6 to 17.6 kW]Roofcurb Adapters RJNA-RXRX-BBCDB21RXRX-B

Page 29

Roofcurb AdaptersOld ModelsOLD CURB MODEL ROOFCURB ADAPTER NEW MODELMEDIUM CABINET (3 TON [11 kW])21 SERIESRXPA-CA21 (1)RXRA-DB21 (2)RXRX-BBCDB21RJNA(

Page 30

ROOFCURBS (Full Perimeter) Rheem’s new roofcurb design can be utilized on 3 through 5 ton [10.6-17.6 kW] models. Two available heights (14" [356

Page 31 - UNIT DIMENSIONS—RJNA- SERIES

[ ] Designates Metric Conversions Features Honeywell Controls Available factory installed or field accessory Gear Driven Direct Drive Actuator Fully M

Page 32

IllustrationST-A0903-01INTEGRAL POWER EXHAUST FOR ECONOMIZER(FIELD INSTALLED ONLY)RXRX-BFF04C—3-5 Ton [10.6-17.6 kW] Models 208-230 V, 1 PH, 60 Hz For

Page 33

DUCT ADAPTERS (3 TO 5 TON [10.6 TO 17.6 kW] MODELS)Rectangular to RoundTransitions (Downflow)RXMC-CB03 – 18" [457 mm] RoundAvailable in 18 inch r

Page 34 - ACCESSORIES—RJNA- SERIES

4INTRODUCTIONINTRODUCTIONENGINEERING FEATURESRJNA- Series Package Heat Pumps1. All models feature Copeland®Scroll®compressors offering maximum reliabi

Page 35

SIDE DISCHARGE CONCENTRIC DIFFUSERRXRN-FA60 (3 to 5 Ton [10.6 to 17.6 kW] Models)For Use With Duct Adapter (RXMC)Model No. A B C D E F G H I J KDuctSi

Page 36 - ACCESSORIES

FLUSH MOUNT CONCENTRIC DIFFUSERRXRN-FA70 (3 to 5 Ton [10.6 to 17.6 kW] Models)For Use With Duct Adapter (RXMC)DIMENSIONAL DATAENGINEERING DATAModel No

Page 37

THERMOSTATS—PACKAGE HEAT PUMPSRECOMMENDED HEAT PUMP THERMOSTATSUnits Without EconomizerHoneywellT7300A1005T8611R1166T874RT841A1209T874G1881 Q674F1360I

Page 38

43WIRING SCHEMATICS—RJNA- SERIES

Page 39

44WIRING SCHEMATICS—RJNA- SERIES

Page 40

45WIRING SCHEMATICS—RJNA- SERIES

Page 41

46WIRING SCHEMATICS—RJNA- SERIES

Page 42 - SPECIFICATIONS

47WIRING SCHEMATICS—RJNA- SERIES

Page 43

48WIRING SCHEMATICS—RJNA- SERIES

Page 44

49WIRING SCHEMATICS—RJNA- SERIES

Page 45

5MODEL IDENTIFICATION—RJNA- SERIESRJNA—A036JK000Electric Heat000 = No Resistance Heat010 = 10 kW Resistance Heat015 = 15 kW Resistance Heat020 = 20 kW

Page 46

GENERAL TERMS OF LIMITED WARRANTYBefore proceeding with installation, referto installation instructions packagedwith each model, as well as complyingw

Page 47

6OPTIONS—RJNA- SERIESOption CodeLow AmbientReduced HeightBaserailsAASide FlowADAF xAK xHail GuardxxBD xxCK x xxBX xAL xNo OptionsFreeze StatTime Delay

Page 48

7GENERAL DATA—RJNA- SERIESModel RJNA- Series A036CK A036CL A036CM A036DKCooling Performance1Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 3

Page 49

8GENERAL DATA—RJNA- SERIESModel RJNA- Series A036DL A036DM A036JK A042CKCooling Performance1Gross Cooling Capacity Btu [kW] 37,600 [11] 37,600 [11] 3

Page 50 - YOUR RETAILER

9GENERAL DATA—RJNA- SERIESModel RJNA- Series A042CL A042CM A042DK A042DLCooling Performance1Gross Cooling Capacity Btu [kW] 42,500 [12.5] 42,500 [12.